JOINTING
Hume's GSBC units are supplied with rebated joints with protruding dowel rods from the lower unit to be joined in a recess on to then upper unit. A 20mm diameter grouting hole is provided for the upper unit to facilitate the grouting procedure. |
| |
DESIGN CONSIDERATIONS AND SPECIFICATIONS
- Design loading requirements for Giant Segmental Box Culvert (GSBC) are in accordance with :
BS 5400 : Part 2 : 1378 modified by (b).
Department Standard ED 31/87, Buried Concrete Box Type Structure, issued by Department Transport (UK) Highway and Traffic.
JKR LTAL (Long Term Axle Load) and SV (Special Vehicle) requirements.
- Reinforced concrete design in accordance with BS 5400 : Pt.4, 1984.
- Concrete characteristic strength at 28 days, fcu = 30 Mpa - 40 Mpa.
- Concrete cover to reinforcement for GSBC = 30mm.
- Soil parameters used in design :-
- Coefficient of the earth lateral pressure at rest = 0.5, bulk density of soil = 19 kN/m3
- Hume's GSBC also complies with proof test load criteria with 2 nos, of 112.5kN loads over an area of 500mm x 150mm, spaced at 1.8meter intervals, placed at any position on the upper unit of the box culvert.
- Hume's GSBC is designed to cater for backfill superimposed dead load not exceeding 4 meters depth (inclusive of pavements) plus 45 units of HB vehicle primary live loads.
- Hydrostatic pressures are eliminated by the provision of a series of 50mm diameter weep holes placed along the centerline of the invert wall.
|
| |
 |
 |
| LOAD TEST IN PROGRESS |
TRANSPORTATION |
|
| |
| |
| DRAINAGES | Page 1 | Page 2 | Page 3 |
| |
|
| Top |
 |
HUME CONCRETE MARKETING SDN BHD (8411-T)
Level 2, Bangunan Pan Global,
No. 1A, Jalan Tandang,
P.O.Box 21, 46700
Petaling Jaya, Selangor.
Hot-line: (603) 7785 5282
Tel: (603) 7783 3068
Fax: (603) 7785 1823
E-mail: Adam Hussein (HIMB-PJ) |
 |
|
|
|
|